For general use in domestic premises, kitchens, offices and industrial equipment where the cables are subjected to low mechanical stress. Suitable for dry, damp and wet installations, including temporary outdoor power. Supply of electricity and communications in buildings and other civil engineering works with the objective of limiting the generation and spread of fire.
-IEC/EN 50525-2-21, CEI 20-107/2-21, CEI 20-19/4
-(CENELEC HD 22.4 S4), BS 6500:2000, NF C 32-102-4
-VDE 0282-4, EN 50575:2014 + EN 50575/A1:2016
Conductor: Class 5 flexible copper conductor
Insulation: EPR (Ethylene Propylene Rubber) EI4
Sheath: PCP (Polychloroprene) EM2
Voltage Rating U/Uo
300/500V
Temperature Rating
Operating: -40°C to +60°C
Minimum installation and use temperature: -25°C
Maximum temperature of short circuit: +200°C
Minimum Bending Radius
Fixed: 4 x overall diameter
Mobile: 6 x overall diameter
NO.OF CORES | NOMINAL CROSS SECTIONAL AREA | MAXIMUM CONDUCTOR DIAMETER | NOMINAL THICKNESS OF INSULATION | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | |
---|---|---|---|---|---|---|
mm2 | mm | mm | mm | kg/km | ||
Minimum | Maximum | |||||
2 | 0.75 | 0.95 | 0.6 | 5.7 | 7.4 | 44 |
2 | 1 | 1.3 | 0.6 | 6.1 | 8 | 55 |
3 | 0.75 | 0.95 | 0.6 | 6.2 | 8.1 | 60 |
3 | 1 | 1.3 | 0.6 | 6.5 | 8.5 | 72 |
4 | 0.75 | 0.95 | 0.6 | 6.8 | 8.8 | 82 |
4 | 1 | 1.3 | 0.6 | 7.1 | 9.3 | 87 |