Stock Code: 874632

Aluminum Covered Line Wire AAAC Conductor

Covered Line Wire are intended primary for the distribution of electrical energy under normal condition of overhead (aerial) installation and service outdoors. Approved for use on insulators for overhead circuits. Otherwise treated as a bare conductor.
The cables maintain optimal performance in typical environmental conditions while ensuring reliable power transmission across overhead networks. Their design prioritizes both electrical efficiency and mechanical durability for sustained service in aerial installations.

Application

AAAC (All Aluminum-Alloy Conductor)‌ serves as a bare overhead conductor specifically engineered for primary and secondary electrical distribution systems. The conductor incorporates high-strength aluminum-alloy material that achieves an optimal strength-to-weight ratio while maintaining superior sag resistance.

Key Performance Advantages:

Enhanced durability‌: The 6201-T81 aluminum-alloy composition provides higher corrosion resistance compared to traditional ACSR (Aluminum Conductor Steel Reinforced)

Structural efficiency‌: Optimized mechanical properties ensure minimal sag under tension, suitable for long-span aerial installations

Standard

-ASTM B399: Specification for Concentric-Lay-Stranded Aluminum Alloy 6201-T81 Conductors. 

-IEC 62004:Conductors for overhead lines – Aluminium and aluminium alloy wires for concentric lay stranded conductors

-ICEA S-61-402: Thermoplastic-Insulated Wire and Cable. 

-ICEA S-66-524: Cross-Linked-Thermosetting-Polyethylene Insulated Wire and Cable. 

-ICEA S-70-547: Weather Resistant Polyolefin Covered Wire and Cable.

Construction

Conductor: AAAC stranded per ASTM B399.

Separator: A suitable opaque tape, as required.

Insulation: Black cross-linked polyethylene (XLPE) or polyethylene (PE).

Maximum operating voltage: XLPE- Normal: 90 °C / PE- Normal: 75 °C

Coverings carry no voltage rating: XLPE- Emergency: 130 °C / PE- Emergency: 95 °C

Maximum conductor operation temperatures: XLPE- Short Circuit: 250 °C / PE- Short Circuit: 150 °C

Technical Parameter

Code NameSizeNo. of wiresInsulation Thickness Overall Diameter Rated Strength Nominal Weight Allowable Ampacity
AluminumLDPEHDPEXLPE
AWG or kcmilmm2mmkgkg/kmkg/kmkg/kmkg/kmA
Walnut6458090.7626.55354036.6469.9471.4371.43105
Butternut4458090.7627.87484458.04107.15107.15107.15135
Hickory4458390.7628.052107058.04120.54122.03122.03135
Pignut2458091.14310.312129392.27175.6177.09177.09180
Beech2458391.14310.643165192.27199.41199.41199.41180
Chestnut1458091.14311.3031610116.3717.27218.76218.76210
Almond1/0458091.52413.1571987146.73282.75284.24284.24235
Pecan2/0458091.52414.4022404184.98348.23349.72349.72290
Filbert3/0458091.52415.7993003233.34430.08433.05433.05305
Buckeye4/0458091.52417.3483787394.21531.27535.74535.74345
Hackberry266.8456751.52418.5173121372.63525.32528.3528.3356
请在浏览器中启用JavaScript来完成此表单。